See the relationship before changing it
The figure reads from left to right. The blue card is thermocouple voltage. The middle card applies this page's rule. The green card is compensated hot temperature. Walk the arrows once: set the input, apply the rule, then read the result with its unit.
The retained audit below checks several chapter fixtures. This model keeps those stated values fixed and changes only thermocouple voltage, so the numeric fixture does not switch without explanation.
Derive the baseline in four named moves
- 1
Name the input. The chapter baseline is 4100 uV.
- 2
Name the relationship. hot temperature = voltage / 41 uV per degree C + 22 degrees C
- 3
Substitute with units. 4,100 / 41 + 22 = 122.0 degrees C
- 4
Read the result. Keep the unit beside the value. Use it only inside the technical boundary on this page.
Predict, then change thermocouple voltage
Try Predict the direction of hot temperature = voltage / 41 uV per degree C + 22 degrees C. Test another thermocouple voltage, then compare compensated hot temperature.
Observe Cold-junction temperature is added after voltage converts by sensitivity. Reset thermocouple voltage to 4100 and compare compensated hot temperature.
Explain Cold-junction temperature is added after voltage converts by sensitivity.
Check yourself
What should you do before trusting a moved-control result?
What does this small model leave out?
1. Read what the voltage represents
A thermocouple voltage responds to a temperature difference between dissimilar-metal junctions. It does not directly report the hot junction's absolute temperature.
2. Build the difference law
SensitivityS says how many microvolts appear per degree Celsius of junction difference.
Forward lawV=S(Thot−Tcold).
InvertThot=V/S+Tcold.
3. Identify the hidden second sensor
The thermocouple wires eventually meet copper at the measurement circuit. A local temperature sensor measures that reference junction so firmware can add it back.
4. Try the cold-junction temperature
TryWarm the instrument enclosure while its catalog-typical Type K voltage remains 4.10 mV.
Observe4,100 µV divided by 41 µV/°C always gives a 100.0 °C difference. At a 22.0 °C cold junction, the hot junction is 122.0 °C.
ExplainIf firmware reports only V/S, its error equals the unmeasured cold-junction temperature. Warming the instrument changes the compensation even when the thermocouple voltage is held fixed.
A Type K Seebeck coefficient is not constant over its whole range.
- standard polynomial or table conversions
- Needs separate evidence
- model both junction metals
- Needs separate evidence
- measure the terminal temperature
- Needs separate evidence
- include wire grade
- Needs separate evidence
- extension cable
- Needs separate evidence
- connector
- Needs separate evidence
- reference-sensor
- Needs separate evidence
- ADC
- Needs separate evidence
- noise
- Needs separate evidence
- thermal-gradient errors
- Needs separate evidence
Use field evidence or a deeper model before release.
5. Work the voltage difference
That is a difference, not yet the hot-junction temperature.
6. Add the reference junction
Reporting 100 °C without compensation would under-read by exactly 22 °C in this linear teaching case.
7. Check yourself
What does 4.10 mV determine by itself?
Why is an ice bath a special reference?
If Tcold rises by 5 °C at fixed V, what happens?
These are the chapter inputs, worked results, and named teaching assumptions.
- 41 µV/°C
- Voltage or voltage-step value
- 4.10 mV
- Voltage or voltage-step value
- 22 °C as catalog-typical Type K teaching values
- Named teaching assumption
- not a full calibration
- Current or responsivity value
The 100.0 °C difference and 122.0 °C compensated result reproduce its worked arithmetic under a local linear approximation.
Phoebe guides