← Back to the chapter · Next detail →
Technical detail · ISA100.11a Fundamentals
Audit the 100 m link budget
Consider a utility-area monitoring point 100 m from a backbone router in open plant space. A simple 2.4 GHz free-space estimate is FSPL = 40.05 + 20 log10(d_m), so 100 m gives about 80 dB path loss. With a 10 dBm transmitter, 2 dBi antenna at each end, and a receiver that can decode near -95 dBm, the rough received level is 10 + 2 + 2 - 80 = -66 dBm, or about 29 dB above that receiver floor. If the enclosure, pipe rack, and fading budget consume 12 dB + 8 dB, only about 9 dB remains.
At 2.4 GHz and 100 m, the more precise free-space loss is 80.05 dB. The same 10 dBm transmitter and two 2 dBi antennas give −66.05 dBm received power, 28.95 dB over the −95 dBm sensitivity floor. Reserving the 20 dB fading budget leaves 8.95 dB, or 7.85× linear headroom.