Sampling before the vibration window
The mathematical gist. A 1200 Hz fault band needs at least 2400 samples/s. At 1600 samples/s, a 2000 Hz component folds to 400 Hz. Separately, the pump sensor’s , 12-bit ADC has , , and an ideal 74.0 dB quantisation ceiling. Sampling protects frequency identity; ADC resolution protects amplitude detail.