Distinguish backhaul loss from gateway power loss
In this teaching pilot, the upstairs equipment sensor sends a uniquely identified maintenance report. Require the upstream maintenance service to record it within 30 seconds of the sensor send. In each run, align the sensor log, gateway receive and queue logs, and maintenance service log to a shared clock, then match entries by report ID.
- Backhaul outage. Disconnect the pilot gateway’s upstream link at 0 seconds and restore it at 20 seconds, leaving gateway power on. The sensor sends at 2 seconds. The gateway logs local receipt and queues the ID because buffering is enabled and there is room. After the link returns, the gateway drains the queue and the service records the ID at 22 seconds. Pass for this report. It took 20 seconds to reach the service.
- Gateway power outage. Repeat with a new ID, keeping the backhaul available and cutting gateway power instead. The sensor logs a send at 2 seconds, but there is no gateway receipt or queue record while it is off. The service still has no record at the 32-second deadline, even after the gateway restarts. Revise. The local gateway buffer cannot hold a report the gateway never received. Test a sensor resend policy or an independently available gateway before accepting this case.
The sensor log shows a send and the gateway log shows local receipt. Check the service log for receipt at that endpoint. Missing log entries alone cannot locate the failure. Check the power and link records against the fault times, and record any shared switch, power feed, or upstream service that could defeat both paths.