Check: Test the installed measurement chain

Knowledge check · self-test

Check: Test the installed measurement chain

Review enclosure lag and traceable sensor selection.

Back to the chapter →

Review enclosure lag and traceable sensor selection.

A sensor may meet one limit but fail another. Predict which specification constrains each use before selecting it.

- **Predict:** A valve fault develops in 20 ms, but the displayed value uses the 64 ms mean. Can the display prove the peak was captured? **Check:** No. The averaging window can smooth or delay the brief pressure event. - **Predict:** The package survives 85 °C storage but lists only 60 °C operating temperature. May it measure at 75 °C? **Check:** Not from the storage rating; operation and unpowered survival are different specification limits.

Back to Sensor Specifications: Summary