Trace a Tap-Water Alarm

Trace a Tap-Water Alarm

Try Use Step to bring tap water into contact with the probes and locate their 2 kΩ resistance in the series circuit.

Dry probes open the loop

Contact conductivity sensing

Dry air is effectively an open circuit between these probes, so no current flows around the loop.

Find the gap between the probes and the matching open switch in the schematic.

Pipe and probes

Cutaway of the pipe and electrical probes The dry probes are separated by air. Tap water bridges the probes Probes Dry air between the probes
Measured effect: conductivity Detection: contact

Series circuit

Illustrative wiring

Series circuit with a supply, resistor, probe junction and supply return The dry probe branch is open. The unloaded junction is at supply potential. + − 3.3 V supply 10 kΩ resistor Supply return Dry probes open At supply potential when dry 2 kΩ wet probes 2.75 V 0.55 V Input Reference

Loop current
I = 3.3 V / (10 kΩ + 2 kΩ) = 0.275 mA

Resistor · 0.275 mA × 10 kΩ = 2.75 V

Wet probes · 0.275 mA × 2 kΩ = 0.55 V

Check · 2.75 V + 0.55 V = 3.3 V

Excitation: supply required Circuit output: analogue

Controller

Suitable analogue input

Input from the junction

Reference wired to supply return

A high-impedance input avoids appreciable loading. It must accommodate the full swing from 0.55 V wet to 3.3 V dry.

Analogue conversion → Threshold decision

Higher input voltage

Dry level

Threshold

Wet level WET

Lower input voltage

Observe Water bridges the dry gap, the open switch becomes a 2 kΩ resistance, and later the voltage strip places the wet level below the threshold and shows WET.
Explain With the controller referenced to the supply return, it reads the 0.55 V drop across the wet probes and uses that lower analogue level to make the WET decision.

Technical boundaries. The circuit represents the wet probes as a fixed 2 kΩ resistance and treats dry air as effectively an open circuit. The controller input is assumed to have high impedance to avoid appreciable loading. Its voltage strip shows the relative levels and leaves the numerical threshold unspecified.