Follow a Tagged Alarm Through a Gateway Outage
Follow a Tagged Alarm Through a Gateway Outage
Try Press Step from the 0 s fault injection to find the first evidence that the gateway path has failed.
When does remote alarm delivery recover?
Recovery drill
Test alarm A
0 s · Fault injected
Surviving local route
Freezer sensorsReadings continue
Local relayAlarm A
↓ From the relay to the gateway boundary
Gateway alternatives
Primary gatewayOffline
Standby gatewayAwaiting failover
Alarm A
Remote flow interrupted
Remote alarm flow
BrokerAlarm A
DashboardAlarm A
Night operator
Expected Alarm A
Receipt pending
Recovery evidence
- Monitor
- Awaiting fault detection
- Retry count
- Path diagnostics
- Standby path
- Awaiting failover
- Path ready at 13 s
- Queue depth
- Possible delay under load
- Operator receipt
- Pending
Separate load illustration · untimed
Routine readings are ahead of an alarm in the queue.
AlarmRoutine readingsQueue exit
Inject the gateway fault
Fault injected at 0 s. Freezer readings still reach the local relay. Remote alarm delivery is interrupted.
Observe The monitor reports detection at 8 s. At 13 s the standby path shows ready and the operator receipt stays pending. At 17 s the Night operator card shows a matching receipt for Alarm A.
Explain The 17 s receipt verifies recovery because it matches the tagged test alarm at the operator. The 13 s standby indicator establishes path readiness, and retry count helps diagnose the failed path.
Technical boundaries. The timed drill follows one tagged test alarm after an injected gateway fault, with freezer readings still reaching the local relay. The queue scene is a separate, untimed illustration of possible delay under load. It supplies no measured queue delay for the drill.