Actuator Safety Checkpoints
Actuator Safety Checkpoints
Tip
Checkpoint: Flyback Protection
Checkpoint: Flyback Protection
You now know:
- The spike comes from V = -L x (di/dt), so faster current interruption makes the voltage larger.
- The worked relay example stores 0.32 mJ and can calculate an 8000 V ideal spike from 100 mH, 80mA, and 1 us.
- The protection choice is physical: give every inductive load a rated decay path before the first live driver test. Use a diode only where the driver and load polarity allow it.
Tip
Checkpoint: Watchdog Timing
Checkpoint: Watchdog Timing
You now know:
- A watchdog is a hardware deadline, not a patient software monitor.
- If a normal loop is 80 ms, a 100 ms watchdog can still be too tight when one iteration takes 150 ms.
- Slow logging, networking, and storage work should be decoupled so the critical control loop can feed the watchdog before the actuator hazard time expires.
Tip
Checkpoint: Fail-Safe Architecture
Checkpoint: Fail-Safe Architecture
You now know:
- The safe state depends on the hazard: heater OFF can prevent overheating, while a freeze-protection load may need independent low-temperature fallback.
- For the 1500W, 120V, 12.5A heater example, the relay, wiring, fuse, enclosure, and 2500V isolation are part of the safety case.
- A controller, cloud link, or app must never be the only path to a safe physical state.