Routine reports and alert wakes

Routine reports and alert wakes

Try Start with Step to reveal the original schedule and locate its first radio start after the shared opening report.

Routine reports and alert wakes

Wake policy

Temperature sketch · dashed line marks the alert threshold

Scheduled report starts; common elapsed-time scaleOrigin10 min20 min30 min
Original
Hybrid

Routine

  • Normal reports no more than 30 minutes apart

Alert

  • Report immediately on threshold crossing
  • Comparator → microcontroller → radio

Reporting contract

The temperature node must send normal reports no more than 30 minutes apart and report immediately when temperature crosses the alert threshold.

Observe The Original row adds reports at 10, 20 and 30 minutes, while the Hybrid row shows only a health report after the opening report, at 30 minutes.
Explain The timer handles routine reports every 30 minutes, and the comparator watches for crossings during microcontroller sleep so the alert path can start between reports.

Technical boundaries. The temperature curves are sketches, and the crossing-to-delivery bracket is unscaled. Sample timing for the routine batch is unspecified. The scheduled starts can be counted in the chart, while total radio starts including alerts, energy use and delivery latency are listed as measurements to collect.