Validating an Office HVAC Spike
Validating an Office HVAC Spike
Try Use Step to bring up the schema and physical range results for the 45.0 C report.
Inspect the incoming samples
Layered data validationOffice HVAC sensor
- 22.0 C
- 22.1 C
- 22.2 CPrevious valid
- 45.0 CUnder review
- 22.3 CLater sample
Temperature bands
Physical range: −10 C to 60 C
45.0 C
Office operating range: 18 C to 26 C
45.0 C
Rate from the previous valid sample
abs(45.0 − 22.2) / 1 second = 22.8 C/s
22.8 C/s > 0.5 C/s
Peer comparison
Nearby zone sensor · 22.4 C ↔ 45.0 C
Nearby zone sensor · 22.4 C ↔ 45.0 C
abs(45.0 − 22.4) = 22.6 C
22.6 C > 3 C
Check results
- SchemaPendingPass
- Physical rangePendingPass
- Operating rangePendingFail · soft flag
- Rate of changePendingFail · hard rule
- Peer checkPendingFail · soft flag
Handling decision
Control
Awaiting decision
22.2 C → Control
Previous valid value
Review
Awaiting decision
45.0 C → Quarantined
- Original value
- 45.0 C
- Canonical unit
- C
- Peer reading
- 22.4 C
- Peer gap
- 22.6 C
Illustrative rule IDs
operating_range, rate_of_change, peer_check
Alert status
Awaiting decision
No alert raised
One isolated office sensor failure. The nearby reading supplies comparison evidence.
Policy · Alert only if a failure repeats or affects multiple sensors.
Observe Schema and physical range turn to Pass before the other checks show failures. The final cards route 22.2 C to Control and put the 45.0 C sample in Review.
Explain The 45.0 C report exceeds the office operating range, jumps faster than the configured rate limit and differs from the nearby reading by more than the peer tolerance, so it is quarantined.
Technical boundaries. This trace covers one isolated failure under the office sensor’s configured thresholds. The nearby sensor supplies a comparison reading, and the review record uses illustrative rule IDs. The alert policy requires a repeat failure or a failure affecting multiple sensors.