Validating an Office HVAC Spike

Validating an Office HVAC Spike

Try Use Step to bring up the schema and physical range results for the 45.0 C report.

Inspect the incoming samples

Layered data validation

Office HVAC sensor

One second apart · oldest to newest →
  1. 22.0 C
  2. 22.1 C
  3. 22.2 CPrevious valid
  4. 45.0 CUnder review
  5. 22.3 CLater sample

Temperature bands

Shared scale · −10 C to 60 C

Physical range: −10 C to 60 C 45.0 C
Office operating range: 18 C to 26 C 45.0 C
Rate from the previous valid sample

abs(45.0 − 22.2) / 1 second = 22.8 C/s

22.8 C/s > 0.5 C/s

Peer comparison
Nearby zone sensor · 22.4 C ↔ 45.0 C

abs(45.0 − 22.4) = 22.6 C

22.6 C > 3 C

Check results

  • SchemaPendingPass
  • Physical rangePendingPass
  • Operating rangePendingFail · soft flag
  • Rate of changePendingFail · hard rule
  • Peer checkPendingFail · soft flag

Handling decision

Control

Awaiting decision

22.2 C → Control

Previous valid value

Review

Awaiting decision

45.0 C → Quarantined

Original value
45.0 C
Canonical unit
C
Peer reading
22.4 C
Peer gap
22.6 C

Illustrative rule IDs

operating_range, rate_of_change, peer_check

Alert status

Awaiting decision

No alert raised

One isolated office sensor failure. The nearby reading supplies comparison evidence.

Policy · Alert only if a failure repeats or affects multiple sensors.

Follow the 45.0 C report through the office sensor’s rules before it reaches control.
Observe Schema and physical range turn to Pass before the other checks show failures. The final cards route 22.2 C to Control and put the 45.0 C sample in Review.
Explain The 45.0 C report exceeds the office operating range, jumps faster than the configured rate limit and differs from the nearby reading by more than the peer tolerance, so it is quarantined.

Technical boundaries. This trace covers one isolated failure under the office sensor’s configured thresholds. The nearby sensor supplies a comparison reading, and the review record uses illustrative rule IDs. The alert policy requires a repeat failure or a failure affecting multiple sensors.